Consulting email:

Sertech001@gmail.com

Rosemount 8732E Field Mount Magnetic Flow Meter Transmitter

A dual-compartment transmitter housing provides isolation from the external environment. Advanced diagnostics and through-the-glass Local Operator Interface offer unparalleled process insight.

0
0
0

A dual-compartment transmitter housing provides isolation from the external environment. Advanced diagnostics and through-the-glass Local Operator Interface offer unparalleled process insight.

  • Sensor compatibility

    Compatible with Rosemount 8705, 8711, and 8721sensors. Compatible with AC and DC powered sensors ofother manufacturers.

  • Transmitter coil drive current

    500mA

  • Flow rate range

    Capable of processing signals from fluids that are travelingbetween 0.04 and 39 ft/s (0.01 to 12 m/s) for both forwardand reverse flow in all sensor sizes. Full scale continuouslyadjustable between –39 and 39 ft/s (–12 to 12 m/s).

  • Conductivity limits

    Process liquid must have a conductivity of5 microSiemens/cm (5 micromhos/cm) or greater.

  • Power supply

    90 - 250VAC, 50/60Hz or 12 - 42VDC

  • Line power fuses

    90-250VAC systems
    1A, 250V, I2t, 1.5 A2s Rating, Fast ActingBussman AGC-1, Littlefuse 31201.5HXP
    12-42VDC systems
    3 Amp, 250V, I2t, 14 A2s Rating, Fast ActingBel Fuse 3AG 3-R, Littelfuse 312003P, Schurter 0034.5135

  • Line power fuses

    15W maximum - DC
    40VA maximum - AC

  • Switch-on current

    AC: Maximum 35.7A (< 5ms) at 250VAC
    DC: Maximum 42A (< 5ms) at 42VDC