Levelflex FMP50 is the instrument for basic applications in liquids which do not place high demands on temperature and pressure ranges or chemical resistance. Particularly in basic supply or storage applications as well as utility processes FMP50 is the best choice. Levelflex FMP50 guided radar is used for continuous level measurement of liquids, pastes and slurries. The measurement is not affected by changing media, temperature changes, gas blankets or vapors.
Measuring Principle | Guided radar |
Characteristic / Application | Basic device |
Rod probe, Rope probe |
Integrated data memory, Factory precalibrated, Reliable measuring for changing medias. |
Specialities | Bluetooth® commissioning, |
Operation and maintenance SmartBlue App |
|
Supply / Communication | 2-wire (HART / PROFIBUS PA/ FOUNDATION Fieldbus) |
4-wire (HART) |
Bluetooth® wireless technology and App (optional) |
Accuracy | Rod probe: +/- 2 mm (0.08 in) |
Rope probe: +/- 2 mm (0.08 in) |
Ambient temperature | -40...+80 °C |
(-40...+176 °F) |
Process temperature | -20...+80 °C |
(-4...+176 °F) |
Process pressure absolute / max. overpressure limit | Vacuum...6 bar, |
(Vacuum...87 psi) |
Main wetted parts | Rod probe: 316L, PPS, Viton |
Rope probe: 316, PPS, Viton |
Process connection | Thread: |
G 3/4, MNPT 3/4 |
Flange: |
UNI Flange |
Sensor length | Rod probe: 4 m (13 ft) |
Rope probe: 12 m (40 ft) |
Max. measurement distance | Rod: 4 m (13 ft) Min DK>1.6 |
Rope: 12 m (40 ft) Min DK>1.6 |
Communication | 4...20 mA HART |
PROFIBUS PA |
FOUNDATION Fieldbus |
Bluetooth® wireless technology |
Certificates / Approvals | ATEX, FM, CSA, CSA C/US, IEC Ex, INMETRO, NEPSI, KC, EAC |
|
Safety approvals | Overfill prevention WHG |
SIL |
|
Design approvals | EN 10204-3.1 |
|
Options | Sensor remote with 3 m/ 9 ft cable, |
Remote operation via SmartBlue App using Bluetooth® |
Application limits | Horizontal storage tank cyl.: |
use coax probe |
Corrosive liquids: |
FMP52 |
High pressure/ temperatures >80°C/176°F; 6bar/87psi: |
FMP51, FMP54 |
Interface measurement |
FMP51, FMP55 |